specification
input
Control system network type
CC-Link
Number of input/output points
16 inputs
Connecting terminal
Spring lock (push-in terminal block)
| Input section |
| Insulation method |
photocoupler isolation |
| Rated input voltage |
DC24V |
| Rated input current |
about 5 mA |
| Working voltage range |
19.2 to 26.4 VDC (ripple rate within 5%) |
| ON voltage |
15V or more |
| ON current |
3mA or more |
| OFF voltage |
3V or less |
| OFF voltage |
0.5mA or less |
| input resistance |
about 4.7 kΩ |
| Input format |
Sink and source shared type |
| Response time (ON→OFF) |
0.2ms or less (at 24VDC) |
| Response time (OFF→ON) |
0.2ms or less (at 24VDC) |
| Common method |
16 points/common |
| Number of occupied stations |
32 points per station (16 points used) |
| I/O unit power supply (voltage) |
20.4 to 26.4 VDC (ripple rate within 5%) |
| I/O unit power supply (current) |
40mA or less (24VDC, when all points are ON) |
| Noise tolerance |
DC type noise voltage ±900Vp-p, noise width 1μs, noise frequency 45Hz, by noise simulator |
| Withstand voltage |
500 VAC for 1 minute between all DC external terminals and ground |
| insulation resistance |
500 VDC between all DC external terminals and ground, 10 MΩ or more by insulation resistance tester |
| mass |
about 145g |
| External connection method |
9-pole 2-piece connector (transmission line, unit power terminal, I/O power terminal, COM1, COM2) |